HWg-WLD Water detector

$347.00$452.00

Wg-WLD is a water leak detector connected to the Ethernet. The sensing cable detects as little as a few drops of a liquid, and can be also used to detect condensation.

SKU: N/A Categories: , , Tags: , ,
Logo

Description

Brand: HW-Group

HWg-WLD is a network-enabled water leak detector with a water-absorbing sensing cable. HWg-WLD features a built-in web server, SNMP support, and e-mail alert to water flooding. HWg-WLD can remotely control a relay output over the network (a relay is switched when a water leak is detected along the sensing cable). HWg-WLD detects water leaks or water floods along the entire length of the sensing cable. The sensing cable detects even the smallest volume of water, ethylene glycol, or other conductive liquid. HWg-WLD can be ordered in two versions depending on the supply of power (power adapter or PoE IEEE 802.3af).

The sensing cable detects as little as a few drops of the liquid, and can be used to detect condensation. After flooding, the cable can be dried and reused.

HWg-WLD features a built-in web server and SNMP support. In case of an alarm, the device sends an e-mail or SNMP trap.

Alarms can be also signaled by switching a remote relay over the Ethernet. When a leak is detected, HWg-WLD activates a relay of a remote Poseidon or Damocles unit (Box-2-Box mode).

Sensing cable can be 2 – 85 m (6.5 – 280 ft) long

Alarm alerts by e-mail, SNMP trap, or by activating a relay output

Detects even the smallest volumes of liquids, sensing cable can be dried and reused

BASIC FEATURES

  • Ethernet: RJ45 (100BASE-T) (PoE version IEEE 802.3af)
  • Web: Built-in web server
  • M2M communication protocols: SNMP, XML, Box-2-Box
  • Remote output: When a water leak is detected, a remote relay is activated over the network (any Poseidon / Damocles)
  • Water flood detector: 2 m (6.5 ft) leader cable +2 m (1.3 ft) sensing cable
  • Power:
    • HWg-WLD: Power adapter
    • HWg-WLD PoE: PoE (IEEE 802.3af) + power adapter (depending on type)
  • Supported software
    • Configuration: UDP Config – IP address configuration and detection (with DHCP)
    • HWg-PD Trigger: Controls other IP devices, redirects alarms to SMS
    • HWg-PDMS: Logging of values, graphs, export to MS Excel, reports
    • CapTemp: Visualization on a map, control of outputs, alarm redirection to SMS
    • >> Third-party SNMP software
      (Nagios, The Dude, Zabbix, IBM Tivoli, HP OpenView, OpManager, IMM (Intellipool Network Monitor), Monitor one, Cacti, MRTG, Opsview, LoriotPro, Axence nvision, Ipswitch WhatsUp, Paessler IPCheck, MSC Operations Manager 2007)
  • For programmers: HWg-SDK contains interface descriptions and examples of using M2M protocols in several programming languages
    (JAVA, PHP, Borland C++ Builder 6.0, Microsoft Visual C++ 6.0, Borland Delphi 6.0, Microsoft Visual Basic & Excel VBA, VB.NET, C code for Linux, JavaScript (AJAX) Microsoft Visual C# 2005 (.NET)

WATER SENSING CABLE

  • The sensing cable detects even the smallest volume of water, ethylene glycol, or other conductive liquid anywhere on the total length of the cable.
  • The sensing cable is terminated with connectors.
  • The following can be combined:
    • Water sensing cable WLD – 2m
    • Water sensing cable WLD – 10m
    • Water sensing cable WLD – 50m
    • Prolong cable – 5m
  • The sensing part of the cable can be up to 85m (280ft) long.
  • The cable can be extended anywhere (even between sensing segments) with a 2-wire cable (max 100m – 330ft).
  • The WLD water detection cable is reusable (needs to be dried).

BOX-2-BOX MODE

HWg-WLD can directly control relay outputs over the network. No additional software is necessary.

  • Supports any Poseidon or Damocles unit
  • State is transferred upon changes as well as periodically (default period is 30s). Uses XML over http.
  • The output must be in the “Manual” mode (no local condition for activating the output)
  • The user configures the remote device IP & port and the remote output ID (ID 151 = Output 1, 154 = Output 4)
  • If the relay is write-protected with a password, the user sets the password for controlling the relay
  • Output control can be tested with the TEST button

APPLICATIONS

Typical applications involve monitoring of coolant piping in air conditioning systems or water detection around pipes in technical areas.

  • Detection of water leaking from pipes (cable runs along the pipes)
  • Detection cable laid along the walls
  • Under raised floors
  • Above suspended ceilings
  • Detection of water leaks in drip trays
  • Detection of water leaks under A/C outlets

The water leak sensing cable can be wrapped around the piping, suspended under the piping, or laid on the bottom of the pipe duct.

Documents:

User Manual WLD

Flyer for WLD

 

Brand

HW-Group

Logo

Additional information

Varieties

Plain unit, Power over Ethernet(PoE)

Reviews

There are no reviews yet.

Be the first to review “HWg-WLD Water detector”